RMMV SeriesRack Mount AC/DC Power SupplyOperating and Installation Instructions52-391 Rev A.02
4.2 Wiring4.2.1 Wire RoutingAll wiring must be installed in accordance with NFPA70 [NEC760] and all local coderequirements.Power Limited wiring requi
Section 5Operating the RMMV Rack Mount Power Supply5.1 Jumper Configuration5.1.1 AC ZonesEach individual AC output zone may be configured for a 24VAC
VOLTAGESELECT24V12VBATDETECTEARTH GNDDETECTAC ONOUTPUT VOLTAGESELECT SWITCHEARTH GOUNDDETECTION ENABLEBATTERY PRESENCEDETECTION ENABLEAC PRESENCEVISUA
5.1.2.1.2 SPS4 Jumper SettingsThe SPS4 has two jumpers for setting its output voltage. It is factory set for 12VDC out. Ifa different voltage is req
5.2.2.1.3 AC FLT This LED illuminates when the AC input voltage falls below approximately 85% of thenominal input voltage setting.5.2.2.1.4 COM FLT Th
5.3 TroubleshootingWARNING - Installation and service should only be performed by a qualified service person andshould conform to all local codes5.3.1
Contact AlarmSafInternal problemVerify correct setting of Bat DetectjumperBat Detect Jumper (JP10) setincorrectly on the internal PS5-MVerify connecti
Section 6Specifications6.1 Electrical Specifications6.1.1 Input Voltage 120VAC nominal6.1.2 Input Power 504W Max 6.1.3 Input Frequency 50-60Hz6.1.4 Mi
Wiring and using an RMBE Series Battery Enclosure with the RMMVThe RMBE Series of Battery Enclosures provides battery backup in a standard 19 inch 2RU
OFFRESETONAC POWERTo reduce the risk of fire, replace interiorfuses only with same type and ratingRISK OF ELECTRICAL SHOCKDO NOT OPENAlarmSaf www.ala
Warnings and NoticesWARNING - To reduce the risk of fire or electric shock, do not expose this productto rain or moistureWARNING - This installation
GlossarySplitting a bulk power supply output into multiple, current limited outputs to prevent asingle circuit failure from talking down an entire sys
Table of Contents20Glossary18Wiring and using an RMBE Series Battery Enclosure with the RMMVAppendices:176.3 Mechanical Specifications176.2 Temperatur
Section 1IntroductionThe RMMV series of rackmount power supplies provides either 24 or 28 VAC for powering CCTV orsimilar low voltage AC operable equi
Section 2Applicable Standards / DocumentsNFPA StandardsNFPA 72 National Fire Alarm CodeNFPA 70 National Electrical CodeUS StandardsUL 294 Access Contr
Section 3System Overview3.1 Electrical Ratings and SpecificationsManufactured ByAlarmSaf65A Industrial WayWilmington, MA 01887Tel: 800 987 1050 978
3.2 Terminal DescriptionsAll terminal strips are removable with locking screws and accept wire sizes from 12-26AWG. Wireshould be sized appropriately
3.2.6 Fault Outputs (Common Fault / AC Fault) Form C Contacts Contacts rated at 1A @ 24VDC, 0.5A @ 120VAC Fault relays employ “fail-safe” operatio
Section 4Installation4.1 Mounting4.1.1 Mount the unit in locations that meet the following temperature and humidity requirements.Do not expose to cond