5.3 Troubleshooting
WARNING - Installation and service should only be performed by a qualified service person and
should conform to all local codes
5.3.1 AC Section Troubleshooting
This is a normal condition. 28V zones
will have a brighter output LED than
24V zones
NormalOutput Zone LEDs vary in brightness
Verify that the zone’s jumper is
present and intact
Missing or damaged jumper
Verify output wiring integrity, then
pull voltage selection jumper for 30
seconds (note it’s position before
removing)
Tripped PTC (Power-Limited models
only)
Verify output wiring integrity, then
replace fuse (Power down unit while
changing fuse)
Blown fuse (Fused models only)
One zone’s green output LED is not lit
and it’s output isn’t present
The power switch also serves as a
circuit breaker. Switch to “Off/Reset”
for 30 seconds, verify output wiring
integrity, then switch back to “On”
Tripped circuit breaker
Verify that the power switch on the
back panel is in the “On” position
Power switch off
Verify power to RackNo power to Rack’s power strip
Verify both ends of the power cord
are plugged in
Power cord unplugged
No green output LEDs lit and no
output voltages present
SolutionPossible CauseCondition
5.3.2 DC Section Troubleshooting
Verify that individual and total output
current is less than rated current
Excessive loading on output
Verify proper switch settingIncorrect switch setting
The output voltage is incorrect
Contact AlarmSafInternal problem
See aboveExcessive loading on output
Verify output wiring integrity and
loading, then replace fuse behind the
front panel. If the unit uses PTC
protection for the output, verify
output wiring integrity and loading,
remove the buss selection jumper for
the output for 30 seconds, then
replace the jumper.
Blown output fuse or PTC
One output voltage not present
Contact AlarmSafInternal problem
Verify total system loading less than
the maximum
Excessive total system loading
The power switch also serves as a
circuit breaker. Switch to “Off/Reset”
for 30 seconds, verify output wiring
integrity, then switch back to “On”
Tripped input circuit breaker
Verify that the power switch on the
back panel is in the “On” position
Power switch off
No output voltages present
SolutionPossible CauseCondition