4.2 Wiring
4.2.1 Wire Routing
All wiring must be installed in accordance with NFPA70 [NEC760] and all local code
requirements.
Power Limited wiring requires that power limited and nonpower limited wiring remain physically
separated. All power limited circuits must remain at least one quarter inch (¼") away from any
nonpower limited circuit wiring.
4.2.2 AC Power Connection
Before using the distributed power outputs, the unit must be connected to the main electrical
power. Use the supplied cord set to plug the unit into the rack power strip and verify that the AC
indicator light built into the main ON/OFF switch on the rear panel and the Green LED's on the
front panel are illuminated when the unit is turned on.
Shut off the electrical power to the location of the unit, and then complete the general
installation.
4.2.3 Field Wiring
Locate the field terminal wiring blocks on the back panel of the unit and remove the terminal
block from the header (there are two locking screws on either end of the terminal block).
Connect the wiring for the connected equipment to the terminal block. The back panel of the
enclosure is labeled with the function and polarity or phase indications (See also section 3.2).
Replace the terminal block on the header and tighten the locking screws.
Figure 4.2.1
C
NCNO
AC
FAULT
COMMON
FAULT
CNCNO
-
+
24V
DC
12V
DC
BAT
+
-
+
-
DC Power Supply
Configure internal jumpers prior to use
See Instruction Manual 52-XXX
OUT8 OUT7 OUT6 OUT5
OUT4
OUT3
OUT2
OUT1
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
Remove load or reset main power to restore PTC protected zones
For fused units remove front panel to replace fuse.
On other than ‘F’ series units, OUT1 thru OUT8 are Class 2 Power Limited
AC POWER
OFF
RESET
ON
Rear Panel
OUT32 OUT31 OUT30 OUT29 OUT28 OUT27 OUT26 OUT25
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
Remove load or reset main power to restore PTC protected zones
For fused units remove front panel to replace fuse.
On other than ‘F’ series units, OUT17 thru OUT32 are Class 2 Power Limited
OUT24 OUT23 OUT22 OUT21 OUT20 OUT19 OUT18 OUT17
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
AC Power Supply
Configure internal jumpers prior to use
See Instruction Manual 52-XXX
12V
BULK
OUTPUT
24V
BULK
OUTPUT
BATTERY
CONNECT
AC FAULT
OUTPUT
COMMON
FAULT OUTPUT
DC
DISTRIBUTED
OUTPUTS
AC
DISTRIBUTED
OUTPUTS
RMMV Series Installation Instructions
7/13/2009, 10:26:56 AM
52-391 Rev A.02
Page 10 of 20
AlarmSaf
65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com
Vue de la page 9
1 2 ... 5 6 7 8 9 10 11 12 13 14 15 ... 19 20

Commentaires sur ces manuels

Pas de commentaire